Fault code
INVT GD270 STo Mal-adjustment fault
Diagnostic context
What STo means on INVT GD270
STo is the GD270 mal-adjustment fault. The manufacturer table associates it with incorrect SM control parameters, inaccurate autotuned parameters or the VFD not being connected to the motor.
Operating context:
Review motor connection and control parameters first, then verify the load and the configured mal-adjustment detection time as listed in the manual.
This diagnostic context is an editorial explanation. The possible causes and recommended checks below are the verified manufacturer troubleshooting content.
Possible causes
- Incorrect SM control parameter settings.
- Autotuned parameters are not accurate.
- The VFD is not connected to the motor.
Recommended checks and actions
- Check the load and ensure the load is normal.
- Check whether control parameters are set correctly.
- Increase the mal-adjustment detection time.
Technical source
INVT GD270 Manual EN - Fault STo — page 280