Fault code
INVT GD270 OUt2 Inverter unit V-phase protection
Diagnostic context
What OUt2 means on INVT GD270
OUt2 indicates V-phase inverter-unit protection. The manufacturer lists interference, poor drive-wire connections and a to-ground short circuit as possible causes.
Operating context:
Inspect the drive wiring first and confirm that its connections are secure. The manufacturer also directs a check for strong interference around peripheral equipment.
This diagnostic context is an editorial explanation. The possible causes and recommended checks below are the verified manufacturer troubleshooting content.
Possible causes
- Misoperation caused by interference.
- Drive wires connected poorly.
- To-ground short circuit occurred.
Recommended checks and actions
- Check drive wires.
- Check whether there is strong interference surrounding the peripheral device.
Technical source
INVT GD270 Manual EN - Fault OUt2 — page 277