Fault code
INVT GD270 ItE Current detection fault
Diagnostic context
What ItE means on INVT GD270
ItE identifies a current detection fault on the GD270. The official table points to poor control board connector contact, a damaged Hall component or an abnormal amplification circuit.
Operating context:
This fault concerns the current-sensing path. The manufacturer checks progress from the connector to the Hall component and then to the main control-board circuitry.
This diagnostic context is an editorial explanation. The possible causes and recommended checks below are the verified manufacturer troubleshooting content.
Possible causes
- Poor contact of the connector of control board.
- Hall component damaged.
- Amplification circuit exception.
Recommended checks and actions
- Check the connector and re-plug.
- Replace the hall component.
- Replace the main control board.
Technical source
INVT GD270 Manual EN - Fault ItE — page 278