Fault code
INVT GD200A OV1 Over-voltage when acceleration
Possible causes
- The input voltage is abnormal.
- There is large energy feedback.
- No braking components.
- Braking energy is not open.
Recommended checks and actions
- Check the input power.
- Check if the DEC time of the load is too short or the inverter starts during the rotation of the motor or it needs to increase the energy consumption components.
- Install the braking components.
- Check the setting of relative function codes.
Technical source
INVT GD200A Manual EN - Fault tracking - OV1 — page 204