Fault code
INVT GD20 OC1 Over-current when acceleration
Possible causes
- The acceleration or deceleration is too fast.
- The voltage of the grid is too low.
- The power of the inverter is too low.
- The load transients or is abnormal.
- The grounding is short circuited or the output is phase loss.
- There is strong external interference.
- The overvoltage stall protection is not open.
Recommended checks and actions
- Increase the ACC time
- Check the input power
- Select the inverter with a larger power
- Check if the load is short circuited (the grounding short circuited or the wire short circuited) or the rotation is not smooth.
- Check the output configuration.
- Check if there is strong interference.
- Check the setting of relative function codes.
Technical source
INVT GD20 Manual EN - P07.27 Current fault type — page 62
INVT GD20 Manual EN - Fault tracking — page 93
Manual tiếng Việt INVT GD20 - Xử lý lỗi — page 82