Fault code
Inovance MD280 Err06 Overvoltage during deceleration
Diagnostic context
What Err06 means on Inovance MD280
Err06 is the MD280 overvoltage during deceleration. The manufacturer lists the input voltage is too high. as one of the documented causes.
Operating context:
Start with the manufacturer troubleshooting sequence. Adjust the voltage to normal range. Cancel the external force or install the braking resistor.
This diagnostic context is an editorial explanation. The possible causes and recommended checks below are the verified manufacturer troubleshooting content.
Possible causes
- The input voltage is too high.
- An external force drives the motor during deceleration.
- The deceleration time is too short.
- The braking unit and braking resistor are not installed.
Recommended checks and actions
- Adjust the voltage to normal range.
- Cancel the external force or install the braking resistor.
- Increase the deceleration time.
- Install the braking unit and braking resistor.
Technical source
Inovance MD280 User Manual EN - Err06 troubleshooting — page 160
Inovance MD280 troubleshooting VI - Err06 — page 9